MODEL
|
MDR-60-5
|
MDR-60-12
|
MDR-60-24
|
MDR-60-48
|
OUTPUT
|
DC VOLTAGE
|
5V
|
12V
|
24V
|
48V
|
RATED CURRENT
|
10A
|
5A
|
2.5A
|
1.25A
|
CURRENT RANGE
|
0 ~ 10A
|
0 ~5A
|
0 -2.5A
|
0-1.25A
|
RATED POWER
|
50W
|
60W
|
60W
|
60W
|
RIPPLE & NOISE (max.) Note.2
|
80mVp-p
|
120mVp-p
|
150mVp-p
|
200mVp-p
|
VOLTAGE ADJ. RANGE
|
5 -6V
|
12-15V
|
24 - 30V
|
48 ~ 56V
|
VOLTAGE TOLERANCE Note.3
|
±2.0%
|
±1.0%
|
±1.0%
|
±1.0%
|
LINE REGULATION
|
±1.0%
|
±1.0%
|
±1.0%
|
±1.0%
|
LOAD REGULATION
|
±1.5%
|
±1.0%
|
±1.0%
|
±1.0%
|
SETUP, RISE TIME Note.5
|
500ms, 30ms/230VAC 1000ms, 30ms/115VAC at full load
|
HOLD UPTIME (Typ.)
|
50ms/230VAC 20ms/115VAC at full load
|
|
VOLTAGE RANGE
|
85 ~ 264VAC 120 ~ 370VDC
|
INPUT
|
FREQUENCY RANGE
|
47 ~63Hz
|
EFFICIENCY (Typ.)
|
0.78
|
0.86
|
0.88
|
0.87
|
AC CURRENT (Typ.)
|
1.8A/115VAC 1A/230VAC
|
INRUSH CURRENT (Typ.)
|
COLD START 30A/115VAC,60A/230VAC
|
LEAKAGE CURRENT
|
<1mA/240VAC
|
PROTECTION
|
OVERLOAD
|
105 ~ 150% rated output power
|
Protection type : Constant current limiting, recovers automatically after fault condition is removed
|
OVER VOLTAGE
|
6.25-7.25V
|
15.6 - 18V
|
31.2-36V
|
57.6 - 64.8V
|
Protection type : Shut down o/p voltage, re-power on to recover
|
FUNCTION
|
DC OK ACTIVE SIGNAL (max.)
|
3.75 ~ 6V / 50mA
|
9 ~ 13.5V / 40mA
|
11.5 ~ 16.5V / 40mA
|
18 ~ 27V / 20mA
|
ENVIRONMENT
|
WORKING TEMP.
|
-20 ~ +70C (Refer to "Derating Curve")
|
WORKING HUMIDITY
|
20 ~ 90% RH non-condensing
|
STORAGE TEMP., HUMIDITY
|
-40 ~ +85C, 10 ~ 95% RH
|
TEMP. COEFFICIENT
|
±0.03%/C (0 ~ 50℃)
|
VIBRATION
|
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
|
SAFETY &EMC (Note 4)
|
WITHSTAND VOLTAGE
|
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
|
ISOLATION RESISTANCE
|
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25C/ 70% RH
|
EMC EMISSION
|
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
|
EMC IMMUNITY
|
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A
|
OTHERS
|
MTBF
|
299.2K hrs min. MIL-HDBK-217F (25℃)
|
DIMENSION
|
40*90*1000mm (W*H*D)
|